Overload Restriction
If the inverter’s output current exceeds a 
preset current level you specify during 
acceleration or constant speed, the overload 
restriction feature automatically reduces the 
output frequency to restrict the overload. 
This feature does not generate an alarm or 
trip event. You can instruct the inverter to 
apply overload restriction only during 
constant speed, thus allowing higher 
currents for acceleration. Or, you may use 
the same threshold for both acceleration and 
constant speed.
When the inverter detects an overload, it 
must decelerate the motor to reduce the current until it is less than the threshold. You can 
choose the rate of deceleration that the inverter uses to lower the output current.
The overload restriction level can be set to a constant or to a variable (analog input). For 
constant values, use B028/B228 = 00 to select parameters B022/B222. For a variable 
overload restriction level, use B028/B228 = 01 to select analog voltage input terminals 
[O]–[L]. In this case, parameters A013 and A014 set the start and end points for the 
linear range of the graph as shown in the graphs below. 
When using the analog input method to set the overload restriction (B028/B228 = 01), 
the inverter does not read settings B022/B222 Overload Restriction Level. Instead, the 
inverter writes the analog input value (in Ampere units) to parameters B022/B222. In 
this way, you can monitor the effective overload restriction value (in Amperes) in real 
time. However, you cannot store the value to B022/B222. If you use the second motor 
function, the inverter displays “
void
” for either B022 or B222 if the parameter’s corre-
sponding motor is not selected via Set or Special Set functions.
Input
State
B022 monitor display
B222 monitor display
Units
[SET] or [S-ST]
OFF
[O] analog input value
void
A
ON
void
[O] analog input value
A
Motor 
Current
Output 
frequency
t
t
Restriction area
0
0
B022
B023
Overload 
restriction 
level
[O]–[L] input
10%
150%
0V
10V
10%
150%
0V
10V
Overload 
restriction 
level
[O]–[L] input
A013 = 0
A014 = 100
A013 = 20
A014 = 80
2
8