Wiring – Warnings for Electrical Practice and Wire Specifications
WARNING: “USE 60/75
qC Cu wire only” or equivalent. For models X200-005S, -007S,
-011S, -022S, -007N, -015N, -015L, -022L, -037L, -055L, -075L.
WARNING: “USE 75
qC Cu wire only” or equivalent. For models X200-002S, -004S, -
002N, -004N, -002L, -004L, -007L, -022H, -030H, -037H, -040H, -055H, -075H.
WARNING: “USE 60
qC Cu wire only” or equivalent. For models X200-004H, -007H, and
–015H.
WARNING: “Open Type Equipment.”
WARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 240V maximum when protected by Class CC, G, J or R fuses or
circuit breaker having an interrupting rating not les than 100,000 rms symmetrical
amperes, 240 volts maximum”. For models with suffix S, N or L.
symmetrical amperes, 240V maximum when protected by Class CC, G, J or R fuses or
circuit breaker having an interrupting rating not les than 100,000 rms symmetrical
amperes, 240 volts maximum”. For models with suffix S, N or L.
WARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 480V maximum when protected by Class CC, G, J or R fuses or
circuit breaker having an interrupting rating not les than 100,000 rms symmetrical
amperes, 480 volts maximum.” For models with suffix H.
symmetrical amperes, 480V maximum when protected by Class CC, G, J or R fuses or
circuit breaker having an interrupting rating not les than 100,000 rms symmetrical
amperes, 480 volts maximum.” For models with suffix H.
HIGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a danger of electric
shock and/or fire.
shock and/or fire.
HIGH VOLTAGE: Wiring work shall be carried out only by qualified personnel.
Otherwise, there is a danger of electric shock and/or fire.
Otherwise, there is a danger of electric shock and/or fire.
HIGH VOLTAGE: Implement wiring after checking that the power supply is OFF.
Otherwise, you may incur electric shock and/or fire.
Otherwise, you may incur electric shock and/or fire.
HIGH VOLTAGE: Do not connect wiring to an inverter operate an inverter that is not
mounted according to the instructions given in this manual.
Otherwise, there is a danger of electric shock and/or injury to personnel.
mounted according to the instructions given in this manual.
Otherwise, there is a danger of electric shock and/or injury to personnel.
WARNING: Make sure the input power to the inverter is OFF. If the drive has been
powered, leave it OFF for five minutes before continuing.
powered, leave it OFF for five minutes before continuing.
CAUTION: Power terminal assignment is different compared to old models such as
L100, L200 series, etc,. Pay attention when wiring the power cable.
L100, L200 series, etc,. Pay attention when wiring the power cable.