Fluke 435 用户手册

下载
页码 140
  
8-1 
Chapter 8 
Volts/Amps/Hertz 
Introduction 
Volts/Amps/Hertz displays a Meter screen with important numerical measuring values. 
The related Trend screen shows the changes over time of all values in the Meter screen. 
Meter screen 
To access the VOLTS/AMPS/HERTZ Meter screen: 
c
 
MENU
 
 
 
 
ENTER
 
 
 
 
 
The Meter screen gives an overview of voltages and currents in all phases. Also 
frequency and Crest Factors are shown. The Crest Factor CF indicates the amount of 
distortion: a CF of 1.41 means no distortion and higher than 1.8 means high distortion. 
Use this screen to get a first impression of power system performance before examining 
the system in detail with other measuring modes. The number of columns in the Meter 
screen depends on the power system configuration. 
The figures in the Meter screen are present values that may update constantly. Changes in 
these values over time are recorded as soon as the measurement is turned on. The 
recording is visible in the Trend screen.