This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. 
Read this manual thoroughly before attempting to unpack, install, or operate your UPS. 
CAUTION!    To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a  temperature  and  humidity  controlled  indoor  area  free  of  conductive 
contaminants.    (Please see specifications for acceptable temperature and humidity range). 
CAUTION!    To reduce the risk of electric shock, do not remove the cover. There are no user serviceable parts inside. 
CAUTION!    Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected. 
CAUTION!    The UPS must be connected to an AC power outlet with fuse or circuit breaker protection.    Do not plug into an outlet that is not 
grounded.    If you need to de-energize this equipment, turn off and unplug the unit. 
CAUTION!    To avoid electric shock, turn off the unit and unplug it from the AC power source before installing a computer component. 
CAUTION!    To  reduce  the  risk  of fire,  connect  only  to  a  circuit  provided  with  20  amperes  maximum  branch  circuit  over  current  protection  in 
accordance with the National Electric Code, ANSI/NFPA 70. 
DO  NOT  USE  FOR  MEDICAL  OR  LIFE  SUPPORT  EQUIPMENT!    CyberPower  Systems  does  not  sell  products  for  life  support  or  medical 
applications.    DO NOT use in any circumstance that would affect operation and safety of life support equipment, any medical applications or 
patient care. 
DO NOT USE WITH OR NEAR AQUARIUMS!    To reduce the risk of fire or electric shock, do not use with or near an aquarium.    Condensation 
from the aquarium can cause the unit to short out. 
 
 
 
 
 
UNPACKING 
Inspect the UPS upon receipt. The box should contain the following: 
(a) UPS unit    x 1 (b) User’s manual    x 1 (c) PowerPanel
®
 Personal Edition software CD    x 1 
(d) USB device cable    x 1 (e) Telephone cable    x 1 (f) Warranty registration card    x 1 
 
 
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
 
1.
  Ensure that the equipment plugged into the outlet does not exceed the UPS unit’s rated capacity (625VA/375W for CP625HG).    If the rated 
capacities of the unit are exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip.     
2.
  There are many factors that can affect the amount of power that your computer system will require.    For optimal system performance keep 
the load below 80% of the unit’s rated capacity. 
 
 
HARDWARE INSTALLATION GUIDE 
1.  Your new UPS may be used immediately upon receipt. As a loss of charge may occur   
during shipping and storage, it is advisable to plug the unit into a wall outlet to charge for 
at least 8 hours before performing a self test. 
2.  With the UPS unit turned off and unplugged, connect your computer, monitor, and any   
other peripherals requiring battery backup into the battery power supplied outlets.    Plug   
the other peripheral equipment (eg. printer, scanner, speakers, etc.) into the full-time surge protection outlets.    DO NOT plug a laser printer, 
paper shredder, copier, space heater, vacuum, sump pump, or other large electrical device into the “Battery and Surge Protected 
Outlets”. The power demands of these devices will overload and possibly damage the unit. 
3.  To protect a fax, phone, or modem, connect a telephone cable from the wall jack outlet to the IN jack   
of the UPS. Connect a telephone cable from one of the UPS OUT jacks to the modem port on the computer.   
The other UPS OUT jack can be used to protect a telephone or fax machine. 
4.  Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet).    Make sure the wall branch outlet is   
protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air   
conditioner, refrigerator, copier, etc.).    The warranty prohibits the use of extension cords, outlet strips,   
and surge strips. 
5.  Press the power switch to turn the unit on.    The Power On indicator light will illuminate green and the unit will “beep” twice. 
6.  If an overload is detected, an audible alarm will sound and the unit will emit one long beep.    To correct this, turn the UPS off and unplug at 
least one piece of equipment from the battery power supplied outlets.    Make sure the circuit breaker is depressed and then turn the UPS on. 
7.  To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 
8.  To store the UPS for an extended period, cover it and store with the battery fully charged.    While in storage, recharge the battery every three 
months to ensure optimal battery life. 
 
 
 
 
 
DESCRIPTION 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
     Battery and Surge Protected Outlets 
The unit has four battery powered/surge suppression outlets to ensure temporary uninterrupted operation of your equipment during a power 
failure. (DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump, or other large electrical device 
into the “Battery and Surge Protected Outlets.” The power demands of these devices will overload and possibly damage the unit.) 
 
 
 
 
 
     Full-Time Surge Protection Outlets 
The unit has four surge suppression outlets. 
     Power Switch 
Press the power button to turn the UPS on or off. 
     Power On Indicator (green) 
This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges and spikes. 
     Electrical Wiring Fault Indicator (red) 
This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring.    If 
this is illuminated, disconnect all electrical equipment from the outlet and have an electrician verify the outlet is properly wired. The unit will 
not provide surge protection without being plugged into a grounded and properly wired wall outlet. 
     Communication Protection Ports 
Communication protection ports will protect any standard modem, fax, or telephone line. (RJ11) 
     Circuit Breaker 
Located on the side of the UPS, the circuit breaker serves to provide overload and fault protection.   
     USB Port to PC 
The port allows connection and communication between the USB port on the computer and the UPS unit.    The UPS communicates its 
status to the PowerPanel
®
 Personal Edition software.    The USB interface is also compatible with the Power Management applications 
provided by Windows 7, Vista, Mac OS X, and Linux. 
     Outlets Designed for AC Adapters 
The UPS unit has four widely-spaced outlets, so AC power adapters can be plugged into the UPS without overlapping adjacent outlets. 
 
 
 
 
 
 
 
Problem 
Possible Cause 
Solution 
Full-time surge protection outlets 
stop providing power to 
equipment. Circuit breaker 
button is projecting from the side 
of the unit. 
Circuit breaker has tripped due to an 
overload. 
Turn the UPS off and unplug at least one piece of 
equipment.    Wait 10 seconds, reset the circuit breaker by 
depressing the button, and then turn the UPS on. 
The UPS does not perform 
expected runtime. 
Battery not fully charged. 
Recharge the battery by leaving the UPS plugged in. 
Battery is worn out. 
Contact CyberPower Systems about replacement batteries 
at tech@cyberpowersystems.com   
The UPS will not turn on. 
The on/off switch is designed to 
prevent damage from rapidly turning 
it off and on. 
Turn the UPS off.    Wait 10 seconds and then turn the UPS 
on. 
The unit is not connected to an AC 
outlet. 
The unit must be connected to a 110/120V 50/60Hz outlet. 
The battery is worn out. 
Contact CyberPower Systems about replacement batteries 
at tech@cyberpowersystems.com 
Mechanical problem. 
Contact CyberPower Systems at 
tech@cyberpowersystems.com
 
The frequency is beyond 47-63Hz. 
Turn the UPS off. Make sure the frequency range is within 
47-63Hz. Or you can turn the UPS on in battery mode. 
PowerPanel
®
 Personal Edition is 
inactive (all icons are gray). 
The USB cable is not connected. 
Connect the USB cable to the UPS unit and an open USB 
port on the back of the computer. 
The USB cable is connected to the 
wrong port. 
Check the back of the computer for an additional USB port.   
Move the cable to this port. 
The unit is not providing battery 
power. 
Shutdown your computer and turn the UPS off.    Wait 10 
seconds and turn the UPS back on.    This should reset the 
unit. 
Additional troubleshooting information can be found at “Support” at 
www.CPSww.com
 
 
 
 
DEFINITIONS FOR ILLUMINATED LED INDICATORS
 
 
 
 
Power ON 
 
Wiring Fault 
 
Alarm 
CONDITION 
On 
Off 
Off 
Normal 
On 
Off 
Beep twice   
every 30 seconds 
Utility Failure- The UPS is providing power to battery power-supplied 
outlets from its battery. 
On 
Off 
Rapid Beeping 
every 1/2 second 
Utility Failure- The UPS is providing battery power.    Rapid beeping 
indicates the unit will run out of power shortly. 
Off 
Off 
Constant tone 
Battery Overload - Occurs when connected equipment exceeds the 
listed  capacity  of  the  UPS.    Turn  the  UPS  off,  unplug  at  least  one 
piece  of  equipment  from  battery  outlets,  wait  10  seconds,  reset  the 
circuit breaker and turn the unit on. 
On/Off 
On 
None 
Electrical Wiring Fault - This indicates a wiring problem with the 
AC  outlet  such  as  bad  ground,  missing  ground,  or  reversed  wiring.   
Disconnect  all  electrical  equipment  from  the  outlet  and  have  an 
electrician check the outlet to insure proper wiring. 
On 
Off 
8 beeps 
Utility Failure- The frequency is beyond 47-63Hz. The UPS will not 
turn on in Line Mode. 
 
 
 
 
 
 
 
 
 
 
 
 
 