Chapter 2 - Start-Up Instructions 
 
 
 
 
 
 
DCS 500B / DCP 500B Operating Instructions 
IV A
  
2 - 1
 
 
General notes 
 
 
 
 
 
CAUTION:  it is absolutely essential that the applicable accident prevention  
 
regulations be observed by the user (in this context, please also  
 
read the chapter entitled "Safety Instructions")! 
 
 
 
 
 
How this chapter is structured 
 
 
For better understanding the individual steps of start-up work are distinguished by 
a) frames 
without 
any additional
 
marking on the left side:  
 
 
These steps of start-up work must always be performed 
(= mandatory start-up work)!
 
 
 
  Example:    
 
 
 
 
 
522 = GERMAN
 
[Only with the SDCS-CON-2 control board & the CDP 312 panel!] 
 
Activates German texts on the display ...........
 
 
 
 
 
 
 
 
 
 
b) frames 
with 
marking on the left side 
(„columns“ shaded in grey)
 
 
These steps of start-up work have to be performed only when the condition stated  
 
 
(as heading) applies to the selected drive configuration!
 After this work has been  
   completed, 
the 
mandatory start-up work 
has to be continued
.
 
 
 
  Example:    
 
 
 
 
Only when connection diagram 1 (Appendix A) is being used! 
 
 
 
 
 
 
 
 
 
 
 
 
906 = 12502
  
 
Function „EMERGENCY STOP“ de-activated ............
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Recommended motor voltages and field voltages 
 
 
• 
Motor voltage U
A
 when the following units are used 
  DCS 501B / DCP 501B: 
U
Amax
 = Line voltage * 1.16 
(2- quadrant unit) 
  DCS 502B / DCP 502B: 
U
Amax
 = Line voltage * 1.05 
(4- quadrant unit) 
• 
Field voltage U
F
 (= max. output voltage) when the following is being used 
 SDCS-FEX-1: 
U
F
 = Line voltage * 0.9  
  If there is a divergence of more than 10 % between the field supply unit's output  
voltage and the rated field voltage U
Frated 
stated on the motor's rating plate, then the  
connecting voltage U
N
 should be reduced, using a matching transformer or a series  
resistor R
v
: 
R
v
 = (0.9 * U
N
 - U
F
) / I
F
   
I
F
 = Rated field current 
  (Note: also suitable for fine-balancing the maximum motor voltage) 
• 
Field voltage U
F
 when the following is being used 
  SDCS-FEX-2 /  
  DCF 503 / DCF 504: 
U
F
 = Line voltage * 0.6 ... 0.8 
• 
Field voltage U
F
 when the following is being used 
  DCF 501B / DCF 502B: 
U
F
 = Line voltage * 0.5 ... 1.1  
  Maximally possible output voltage U
Amax
 using 
  DCF 501B / DCF 502B: 
U
F
 = Line voltage * 1.35
 
 
3ADW000055R0401_DCS500B_Operating Instruction_e_d