5.3.1.1 Auto Restart 
Sends the command to the UPS to configure the auto restart function.  
5.3.1.2 UPS Buzzer 
Sends the command to the UPS to configure the buzzer function.  
5.3.1.3 Low Battery 
The set value is compared to the received value from the UPS. If the received battery 
level is lower than the assigned value then the card sends the Low Battery Warning.  
5.3.1.4 UPS Shutdown Action 
The set value is compared to the received value from the UPS. If the Power Fail or Low 
Battery event occurs then the card sends the assigned shutdown delay time to the UPS. 
5.3.1.5 Smart Shutdown 
Initiates a signal for the server to shutdown.  After the user-defined Estimated OS 
Shutdown Delay, the output power is switched off.  SNMP-NV6 Client or SNMP 
Shutdown Agent must be used on the server for it to be properly shutdown.  The 
Estimated OS Shutdown Delay includes the assigned countdown delay in the shutdown 
software plus the duration of OS shutdown process.  When the Shutdown Agent receives 
the Smart Shutdown signal, the low battery settings will be used to process the shutdown 
procedure. 
5.3.1.6 Battery Replacement Date 
After the battery replacement dates are assigned, the card then sends the command to 
store these dates in the UPS. 
5.3.1.7 External Battery Pack 
If you are using an External Battery Pack with this UPS, the UPS must be configured so 
that; the UPS will report the correct estimated runtime.