UPS INSTALLATION PLAN AND UNPACKING
EATON Powerware
®
 9395 UPS (1000–1100 kVA) Installation and Operation Manual  
S
  164201764 Rev 1 www.powerware.com
3−18
There is no manual DC disconnect device within the UPS.
A battery disconnect switch is required for battery systems and may also be required
by NEC or local codes. The battery disconnect switch should be installed between the
battery and the UPS.
External DC input overcurrent protection and disconnect switch is to be provided by
the customer. Table 3-16 and Table 3-17 list the maximum ratings for continuous-duty
rated circuit breakers satisfying the criteria for both. Recommended disconnect size is
based on a maximum full load discharge time less than 3 hours. For longer discharge
times a larger disconnect may be required.
Table 3-16. Recommended DC Input Battery Disconnect Ratings – Common Battery
UPS Model
Input Rating
480V
Powerware 9395−1100/1000
2500A
Powerware 9395−1100/1100
3000A
Powerware 9395−1100/650
Powerware 9395−1100/750
Powerware 9395−1100/825
2000A
Table 3-17. Recommended DC Input Battery Disconnect Ratings – Separate Battery
UPS Model
Input Rating
(each UPM)
480V
Powerware 9395−1100/1000
700A
Powerware 9395−1100/1100
Powerware 9395−1100/650
Powerware 9395−1100/750
Powerware 9395−1100/825
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC.
Rated battery current is computed at 2 volts per cell.
The battery wiring used between the battery and the UPS should not allow a voltage
drop of more than 1% of nominal DC voltage at rated battery current.