Powerware 9315 用户手册

下载
页码 92
20
Powerware 9315 (200 kVA---300 kVA) Operation
164201036 Rev. D 041500
Using the LCD Screen
The LCD screen at the top of the Monitor Panel provides an operator interface with
the UPS. Figure 9 identifies the display fields discussed in the following sections.
Uninterruptible Power System
System Normal
Alarm:
None
Notice: None
Meters
System
Load Amps
Events Statistics Graphics Setup
Input
Output
Bypass
Battery
VAB
480
VBC
VCA
KW
379
KVA
399
IA
IB
IC
FREQ
60.0
PF
0.95
V
540
I
000
Meters
480
480
480
480
480
VAB
480
VBC
VCA
480
480
IA
IB
IC
361
361
361
IN
000
VAB
480
VBC
VCA
480
480
FREQ
60.0
KVA
300
KW
240
PF
0.80
Battery
04 MAY 1997
14:23:45
100%
Percent
A
E
D
C
B
F
G
Figure 9. Parts of the LCD Screen (Typical for Powerware 9315 300 480/480V Unit)
A
The
UPS status area contains three lines that display the current state of the UPS. The first
line shows the present operational mode of the UPS. The second line shows the highest level
of the current active alarms, and the third line shows any notices the UPS has posted. (For
more information about alarms and notices, refer to Chapter 11, “Responding to System
Events.”)
B
The
battery charge box shows the percentage of battery capacity available.
C
The
menu box shows the currently selected menu and lists the options available on that
menu. The title at the top of the menu box is also shown below on the menu bar (
E). Press
the
and
pushbuttons to scroll up and down through the options in the menu box.
D
The currently selected
option is highlighted in the menu box. Press the
and
pushbuttons
to move the highlight up or down. The data in the information area (
G) changes accordingly.
E
The
menu bar lists the titles of the menus. The title of the menu currently displayed in the
menu box is highlighted. When you press the
and
pushbuttons to move the highlight
left or right, the data in the menu box and the information area change accordingly.
F
The
timestamp shows the current date and time. This date and time are recorded in the Event
Log when a notice or alarm is activated.