Powerware 9315 用户手册

下载
页码 92
75
Powerware 9315 (200 kVA---300 kVA) Operation
164201036 Rev. D 041500
Product Specifications
The UPS systems are housed in freestanding, double-front cabinets
with safety shields behind the doors. The UPS systems are available in
both 50 Hz and 60 Hz, with various output power ratings. Smaller models within a
system may be upgraded in the field to larger models:
System
Models
Notes
Powerware 9315 200
200 kVA
50 Hz or 60 Hz (400V models only)
Powerware 9315 225
225 kVA
60 Hz only
Powerware 9315 250
200 kVA & 250 kVA
50 Hz or 60 Hz (400V models only)
Powerware 9315 300
225 kVA & 300 kVA
60 Hz only
The following sections detail the input, output, environmental, and battery
specifications for the UPS.
System Input
Operating Input
Voltage
(Nominal +10/--15%)
480 VAC for operation from 408 VAC to 528 VAC (60 Hz only)
400 VAC for operation from 340 VAC to 440 VAC (50/60 Hz only)
600 VAC for operation from 510 VAC to 660 VAC (60 Hz only)
Operating Input
Frequency Range
3 Hz of nominal (50 Hz or 60 Hz)
Operating Input
Current
Battery Charge:
125% of full load for overload + battery charge
Actual load + 25% of full load for battery charge
Reduced for Generator:
Adjustable, set to 102%
Input Current
Harmonic Content
10% THD at full load (with input filter option installed)
Power Walk-In
Adjustable 3---60 second rectifier ramp-up to full utility load
Power Factor
Minimum 0.95
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801---4