Powerware 9315 (200 kVA---300 kVA) Operation
164201036 Rev. D 041500
Using the LOAD OFF Pushbutton
Load Off is initiated by the covered, red
LOAD OFF
pushbutton on the Monitor Panel. This pushbutton is protected by
a clear plastic shield to prevent accidental activation. In an emergency, you can
press this pushbutton to instantaneously open the input breaker and interrupt UPS
output. The UPS is cut off from utility power, and your critical load is de-energized.
All power to the critical load is lost. The UPS (including Bypass) remains locked off
until you reset the
LOAD OFF pushbutton.
WARNING:
All power to the critical load is lost when you press this pushbutton. You should
use this feature only in an emergency or when you want to de-energize the critical
load.
To restart the UPS after pressing the
LOAD OFF pushbutton, follow the procedure
“Resetting the UPS System after Load Off” of this chapter before starting the UPS.
NOTE: The Remote Emergency Load Off option functions the same way as the
LOAD OFF pushbutton on the Monitor Panel.
To Use the LOAD OFF Pushbutton
1.
Raise the clear plastic shield covering the red
LOAD OFF pushbutton on the
Monitor Panel.
2.
Press the
LOAD OFF pushbutton.
The breaker and contactors open (you can hear them opening). The
CB1 switch
trips, and the Load Off
PUSH TO RESET pushbutton on the UPS Control Panel pops
out. The UPS system shuts down.
Resetting the UPS System after Load Off
CAUTION:
Do not attempt to restart the system after Load Off until the cause of the
emergency has been identified and cleared.
The Load Off
PUSH TO RESET pushbutton is a small white button on the UPS
Control Panel. The
PUSH TO RESET pushbutton pops out and the CB1 switch
trips when the LOAD OFF pushbutton on the Monitor Panel is activated.
To reset the UPS system:
1.
Press the Load Off
PUSH TO RESET pushbutton until it clicks in and remains
recessed.
2.
Move the
CB1 switch from the center (tripped) position to OFF. The switch
should be difficult to move from the
TRIPPED position.
3.
The UPS system is now reset. To restart the UPS system, follow the procedure
in Chapter 4, “Starting and Stopping the UPS.”