Powerware 5075 kVA 用户手册

下载
页码 162
32
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
4.
Connect RIM wiring to the terminal block using the terminations shown in
Table E.
5.
Contact your local field service office for verification and testing of the RIM
and its connections prior to making connections with J1---J4.
You can order interface cables separately for connecting to the 15-Pin D-Sub
Connectors.
6.
Repeat steps 1 through 5 for each RIM you are installing.
7.
If you are installing an RMP or SCM in addition to an RIM, proceed to Chapter
4 or 6, respectively; otherwise, secure the UPS cabinet by reversing the steps
contained in procedure “To Prepare the UPS for Wiring to an RMP, RIM, SCM,
or Remote EPO” of Chapter 2.
Table E. RIM Wire Terminations
From RIM A
To UPS
Remarks
TB1---4
TB3---1
TWISTED WIRES (4)
TB1---5
TB3---2
TWISTED WIRES (4)
1---2 TURNS PER
TB1---6
TB3---3
1 2 TURNS PER
3 INCHES
TB1---7
TB3---4
From RIM B (if used)
To UPS
Remarks
TB1---4
TB3---5
TWISTED WIRES (4)
TB1---5
TB3---6
TWISTED WIRES (4)
1---2 TURNS PER
TB1---6
TB3---7
1 2 TURNS PER
3 INCHES
TB1---7
TB3---8