Table 8.4   Complete Shutdown (continued) 
Step Procedure 
LCD/LED 
Status (After Execution) 
8 Turn 
off 
the 
precharge 
circuit switch (6CH). 
 
Wait about 20 minutes 
until the DC capacitor 
has been discharge.* 
 
10 
Using the scroll keys, 
change the display 
screen and check to 
make sure that the DC 
voltage is 0V (see 
Section 7.2.4 “LCD 
Screen Switching” on 
page 24). 
 
11 
Set the control power 
supply switch (8A) to 
the OFF position. * 
→ Complete shutdown
 
Nothing at all is displayed on the LCD and all LEDs are 
unlit. 
This operation is different from that displayed in the help message on the screen.   
Be sure to perform the operation as described here. 