8.3.7  Changing the Power Supply to Maintenance Bypass 
This UPS must be completely shut down when performing maintenance and inspections. In 
such cases, the power supply to the load will go through the maintenance bypass. Table 8.8 
shows the procedure used to change the power supply to this maintenance bypass. Table 8.9 
shows how to change the power supply from the maintenance bypass back to the UPS. 
Table 8.8   Changing From UPS to maintenance Bypass Power Supply 
Step Procedure 
LCD/LED 
Status (After Execution) 
1-3 
Same as steps 1-5 in Section 8.3.4 "Stop." 
4 Turn 
ON 
maintenance 
bypass AC circuit 
breaker 52M. *
,
**
 
 
5 Perform 
steps 
through 11 in Table 8.4 
“Complete Shutdown” 
on page 34 to shut 
down the UPS 
completely. 
→Change to 
maintenance bypass 
power supply 
complete.
 
When the UPS is shutdown completely, nothing at all will be 
displayed on the LCD screen and all LEDs will be unlit. 
 
 
During load operation, always operate the circuit breakers in the following order :   
  52M ON
→52lL OFF→ 52C OFF 
** When power is supplied to the UPS, circuit breaker 52M cannot be turned on. 
 