Toshiba 125 用户手册

下载
页码 120
94
G8000 Series Installation and Operation Manual
TOSHIBA
G8000 Series UPS
Installation Planning Guide for 300kVA UPS
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K30KK6XSxx)
Rev. 2.3
Page 1 of 3
G8000-IPG-300kVA
General Mechanical Information
Dimensions
(W  x D x H)
Weight
Floor 
Loading
Approximate Full-Load
Heat Rejection
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Inches
Lbs.
Lbs./ft.
2
Btu/Hr
Top
Front
Bottom
Sides
Back
76.8” x 35.7” x 79.2”
4,575
240
89,011
15.75”
43.5”
0”
0”
0”
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power Demand
Normal Mode (Recharge Mode)
Suggested External 
Overcurrent Protection
External Feeder Wire Size:  Min. – Max. Per Phase
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
326 (329)
>0.99
396 (409)
600 AT
(2) 250 kcmil  – (3) x 2/0
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)
Maximum Input Power 
Demand
Suggested External 
Overcurrent Protection
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
300
1.0
361
500 AT
(2) 300 kcmil – (3) x 2/0 (2) 300 kcmil // (4) x 300 kcmil – (6) x 2/0
DC Backup Input (Battery - 360VDC Nom.)
Backup System DC Capacity for Full 
Load Output
Maximum Discharge 
at Full Load Output
Suggested External 
Overcurrent Protection*
External Feeder Wire Size:  
Min. – Max. 
kWB
Amps DC
Amps
AWG or kcmil at 75º C Temp. Rating
Battery
323
1073
1200 A
(4) x 300 kcmil – (4) x 350 kcmil
* If required.  Most Battery Cabinets are equipped with built-in breakers.
AC Output (480/277V 3-Phase / 4-Wire)
Rated Output Power
Suggested External 
Overcurrent Protection
External Feeder Wire Size:  
Min. – Max. Per Phase // Min. – Max. for Neutral
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
300
1.0
361
450 AT
(2) 300 kcmil – (3) x 2/0 (2) 300 kcmil // (4) x 300 kcmil – (6) x 2/0
Important Notes:
1. CABLE ACCESS – Top only.
2. Maximum Current required at Primary AC Input based on full
load output and maximum battery charging current.
3. Output load conductors are to be installed in separate 
conduit from input conductors.
4. Control wires and power wires are to be installed in separate 
conduits.
5. Recommended AC input and output overcurrent protection 
based on continuous full load current per NEC.
6. Wiring shall comply with all applicable national and local 
electrical codes.
7. Grounding conductors to be sized per NEC Article 250-122.  
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
- Alternate AC Input: 3φ, 4-wire + ground.
- AC Output: 3φ, 4-wire + ground.
- DC Input: 2-wire (Positive/Negative)  + ground.
8. Nominal battery voltage based on the use of VRLA type 
batteries (2.0 volts/cell nominal).
9. Maximum battery discharge current based on lowest 
permissible discharge voltage of 1.67 VPC.
10. DC wires should be sized to allow not more than a 2-volt 
drop at maximum discharge current.
11. Weights do not include batteries or other auxiliary equipment 
external to the UPS.
12. Cable sizing calculations based on the following assumptions:
- Minimum size is smallest size based on ampacity at 30 °C.
- Maximum size cable is based on cable bend radius 
limitations at the UPS terminals.
- Neutral sized for 2X phase current.
- Not more than 3 current-carrying conductors installed in 
conduit in ambient temperature of 30 °C.
- Temperature rating of copper conductors/terminals: 75 °C.
- Reference: 2005 NEC Handbook, Table 310.16. 
NOTE:  Consult latest edition of applicable 
national and local codes for possible 
variations.
13. Ratings of wires and overcurrent devices are suggested 
minimums.  Consult with a registered Professional Engineer 
within your local area for proper size selections.
 
TOSHIBA
 
INTERNATIONAL CORPORATION
13131 West Little York Road
Houston, TX 77041
Telephone: (877) 867-8773
Fax: (713) 896-5212
Web Site:  
www.toshiba.com/ind
300kVA IPG