G8000 Series Installation and Operation Manual
WARNING
While operating in the inverter mode, placing the input breaker 
in the “OFF” position will switch the UPS to the battery backup 
mode.
The output of the UPS will continue uninterrupted to the load. The unit 
must be in the bypass mode at the time that the breaker is placed in 
the “OFF” position for the UPS to shutdown power to the load.
CAUTION
After an Emergency Power Off (EPO), DO NOT reset the breaker 
until the UPS internal circuits have been fully discharged.
The UPS could be damaged if the unit is not fully discharged before 
the breaker is reset.
input frequency range must be within the rated input frequency range.
3) The UPS should not be used with a load that has a rated input that is greater than the 
rated output of the UPS.
4)  If using the UPS to provide power to motors that require high starting current or with 
motors that require a long starting time, call Toshiba support for guidance in over sizing 
the UPS for lock rotor current.
5) DO NOT insert metal objects or combustible materials in the ventilation slots of the UPS.
6) DO NOT place, hang, or paste any objects on the exterior surfaces of the UPS.
7) The capacitors in the UPS maintain a residual charge for a while after turning the UPS 
off. The required discharge time for each UPS typeform is provided via a cabinet label 
and a 
CHARGE LED. Wait for at least the minimum time indicated on the label and 
ensure that the 
CHARGE LED has gone out before opening the door of the UPS once 
the UPS power has been turned off.
8) DO NOT attempt to disassemble, modify, or repair the UPS. Call your Toshiba sales 
representative for repair information.
9) Turn the power on only after installing 
ALL of the covers.
10) DO NOT remove any covers of the UPS when power is on.
11) If the UPS should emit smoke or an unusual odor or sound, turn the power off immediately.
12) Warning signs should be placed on or near the load as a notification that the load is 
being powered by the UPS.
13)  Additional  warnings  and  notifications  shall  be  posted  at  the  equipment  installation 
location as deemed required by 
Qualified Personnel.