G8000 Series Installation and Operation Manual
14.1    Operation Types
The operation types are summarized below.
TABLE 14.1 OPERATION TYPES
Operation
Description
Complete Shutdown
Turn off the control power supply. Shut down the UPS 
completely.
Float / Equalize Charge Changing the battery recharge mode between float charge and 
equalize charge.
Protection Charge
Automatic recharge mode transition from protection charge to 
float charge.
Startup
Starting up and operating the UPS.
Stop
Stop the inverter and chopper/charger.
Switch Power Supply
Switching power supply source between UPS and Bypass.
14.2    Pre-operational Check
Before operating the UPS:
1.  Make sure all covers/panels are in place and secured.
2.  Make sure the temperature in the UPS/Battery room is within specified limits.
3.  Before starting the UPS, check the power source to make sure AC input power is on.
4.  Make sure battery breaker’s auxiliary A-contact is connected to the terminal block TB1.
CAUTION
Perform the pre-operational check before operating the UPS.