Black Gold Single Phase Uninterruptible Power Supply Systems 
Guide Specifications 
2.0kVA Industrial Rackmount 
 
Page 2 of 5 
waveform modulated by the PWM control using the 16 KHz switching frequency 
sinewave.  The PWM-Modulated voltage waveform is transformed into a sine voltage 
waveform by the inductive component of the inverter transformer and by the capacitive 
component of the capacitor filter.  The chopper, inverter, and charger use the IGBT with 
a self-extinguishing function and a high switching speed. 
 
 
4.2 
Modes of Operation 
 
 
4.2.1 
Emergency (Battery Backup) 
In the event the AC power from the utility system fails, the DC power is supplied from 
the batteries to the chopper and to the inverter to provide a continued and stable AC 
power supply to the load without interruption. 
 
 4.2.2 
Normal 
(Inverter) 
The rectifier converts AC to DC to power the inverter, which supplies power to the 
critical load and simultaneously float charging the batteries. 
 
 4.2.3 
Battery 
Charge 
The charger will float charge the batteries while no load is being powered by normal 
mode. 
 
 4.2.4 
Static 
Bypass 
The load is being powered by an alternate source by being transferred from normal mode 
to bypass mode by the bypass switch.  This mode is used during overload and 
maintenance repair.  Power is conditioned by M.O.V.'s and a line filter during bypass 
operation. 
 
5.0 UPS 
Input 
 
 
5.1 
System Rating  The UPS's are sized to supply a load with a power factor of 0.70. 
 
 5.2 
Electrical 
Requirements 
 
 
Voltage: 
120 VAC Single Phase  +10%/-30% 
 
 
 
Frequency: 
50 or 60 Hz    +/- 5 Hz 
 
 
 
Input Harmonic Distortion: 
less than 10% THD (current) 
 
 
 
Input capacity:  1.0 times output capacity 
 
 
 
Input power: 
approximately 1.0 power factor (unity) 
 
 5.2.2 
Battery 
Bus 
 
 
 
Volts:    
2.0 KVA 72 VDC nominal 
 
 
 
Backup time: 
6 mins @ full load/18 mins @ half load