Tripp Lite SU750RTXLCD2U 用户手册

下载
页码 7
4 post installation hardware included, Optional 2POSTRMKITWM enables 2 post rack / wallmount installation, Optional 2-9USTAND
enables tower placement
Single line TEL / Network surge suppression
Electronic bypass maintains utility output during a variety of UPS fault conditions
Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries
are expired and require replacement
Frequency regulation / conversion mode offers generator-compatible frequency correction or conversion of frequency from 50 to 60Hz or 60
to 50Hz 
Built-in USB, RS-232, contact-closure and optional SNMPWEBCARD accessory monitoring options
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
750
Output kVA
capacity (kVA)
.75
Output Watt
Capacity (watts)
675
Output power
factor
0.9
Output Capacity
Details
ON LINE MODE: Maximum output capacity ratings are reduced for some nominal voltage settings (127/120/115/110V
675 watts, 100V 608 watts). FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are
reduced in frequency regulation / conversion mode (127/120/115/110V 472 watts / 100V 425 watts).
Crest Factor
3:1
Nominal Output
Voltage(s)
Supported
100V; 110V; 115V; 120V; 127V
Nominal Voltage
details
120V factory-default nominal voltage
Frequency
compatibility
50/60 Hz (auto-selectable); Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency
compatibility
details
ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output
matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds
+/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. FREQUENCY
REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency input is 40 to
70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY MODE: Output is
regulated to +/-0.05Hz.
Output voltage
regulation (line
mode)
+/- 2%
Output voltage
regulation
(Economy line
mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 3%
Built-in UPS
output receptacles
6 5-15R outlet(s)