G8000 Series Installation and Operation Manual
TABLE 13.3 - CONTINUED
MEASUREMENT SCREENS
O/P CURRENT (PEAK)
Shows the peak output current peak (%) for each phase.
U     50[%]
V     50[%]
W    50[%]
Peak value of output current
 x 100 [%]
RMS value for rated current x 1.41
AC INPUT
Shows the AC Input Voltage (line-to-line) and frequency.
AC I/P-V  480[V]
FREQ.   60.0[Hz]
BYPASS INPUT
Shows the Bypass Input Voltage (line-to-line voltage) and 
frequency. 
BYP I/P-V  480[V]
FREQ.    60.0[Hz]
DC INPUT
Shows the internal DC bus voltage, battery voltage and 
battery current.
The battery current value displayed is negative during 
recharge and positive during discharge.
DC-V    632[V]
BATT-V  400[V]
BATT- I    0[A]
MODE COUNT
Shows the cumulative UPS operation time, the 
cumulative battery backup time and the number of battery 
backup operations.
UPS              35[H]
BATTERY    56[MIN]
                     32[TIM]
CLOCK
The current time is displayed if there are no faults 
recorded, or after the reset button is pressed.
Date is displayed in the mm-ddyyy format.  The unit does 
not calculate daylight savings time.
Time is displayed in the 24-hour format (e.g. 1:58 P.M. = 
1358 Hrs.)
TIME 03-24-06 13:58