APC SUA1500RMJ2UB 用户手册

下载
页码 17
  3: U
SER 
C
ONFIGURABLE 
I
TEMS
 
N
OTE
:
  
S
ETTINGS ARE MADE THROUGH SUPPLIED 
P
OWER
C
HUTE SOFTWARE OR OPTIONAL 
S
MART 
S
LOT 
 
ACCESSORY CARDS
F
UNCTION
 
F
ACTORY
 
D
EFAULT
 
U
SER 
S
ELECTABLE 
C
HOICES
 
D
ESCRIPTION
 
Automatic Self-Test 
Every 14 days  
(336 hours) 
Every 7 days 
(168 hours), 
On Startup Only, No 
Self-Test 
This function sets the interval 
at which the UPS will execute 
a self-test. Refer to your soft-
ware manual for details. 
UPS ID 
UPS_IDEN 
Up to eight characters to 
define the UPS 
Use this field to uniquely 
identify the UPS, (i.e. server 
name or location) for network 
management purposes. 
Date of Last Battery Re-
placement 
Manufacture 
Date 
Date of Battery Replace-
ment 
mm/dd/yy 
Reset this date when you 
replace the battery module. 
Minimum Capacity Before 
Return from Shutdown 
0 percent 
15, 25, 35, 50, 60, 75, 90 
percent 
The UPS will charge its bat-
teries to the specified percent-
age before return from a shut-
down. 
Voltage Sensitivity 
The UPS detects and reacts 
to line voltage distortions 
by transferring to battery 
operation to protect the 
connected equipment. 
Where power quality is 
poor, the UPS may fre-
quently transfer to battery 
operation. If the connected 
equipment can operate 
normally under such condi-
tions, reduce the sensitivity 
setting to conserve battery 
capacity and service life. 
 
Brightly lit: UPS is set to 
high sensitivity. 
Dimly lit:    UPS is set to 
medium sensitivity. 
Off:             UPS is set to 
low sensitivity. 
 
To change the UPS sensitiv-
ity, press the voltage sensitiv-
ity button 
 (rear panel). 
Use a pointed object (such as 
a pen) to do so. 
You can change the sensitiv-
ity level through PowerChute 
software. 
Alarm Delay After Line 
Fail 
5 second delay 
30 second delay, At Low 
Battery Condition, No 
To avoid alarms for minor 
power glitches, set the alarm 
delay. 
Shutdown Delay 
20 seconds 
0, 60, 120, 240, 480, 720, 
960 seconds 
Sets the interval between the 
time when the UPS receives a 
shutdown command and ac-
tual shutdown. 
   
7