This equipment is designed to permit the connection of the grounded conductor of 
the DC supply circuit to the grounded conductor at the equipment.  If this 
connection is made, all of the following conditions must be met: 
1.  This equipment shall be connected directly to the DC supply system 
grounded electrode conductor or to a bonding jumper from a grounded 
terminal bar or bus to which the DC supply system grounding electrode 
conductor is connected. 
2.  This equipment shall be located in the same immediate area (such as, 
adjacent cabinets) as any other equipment that has a connection between 
the grounded conductor of the same DC supply circuit and the grounding 
conductor, and also the point of grounding of the DC system.  The DC 
system shall not be grounded elsewhere. 
3.  The DC supply source shall be located within the same premises as this 
equipment. 
4.  Switching or disconnecting devices shall not be in the grounded circuit 
conductor between the DC source and the point of connection of the 
grounding electrode conductor. 
Rackmount Precautions 
1.  Elevated Operating Ambient - If installed in a closed or multi-unit rack 
assembly, the operating ambient temperature of the rack environment may 
be greater than room ambient. Therefore, consideration should be given to 
installing the equipment in an environment compatible with the maximum 
ambient temperature (Tma) specified by the manufacturer.  
2.  Reduced Air Flow - Installation of the equipment in a rack should be such 
that the amount of air flow required for safe operation of the equipment is 
not compromised.  
3.  Mechanical Loading - Mounting of the equipment in the rack should be 
such that a hazardous condition is not achieved due to uneven mechanical 
loading.  
4.  Circuit Overloading - Consideration should be given to the connection of 
the equipment to the supply circuit and the effect that overloading of the 
circuits might have on overcurrent protection and supply wiring. 
Appropriate consideration of equipment nameplate ratings should be used 
when addressing this concern.  
5.  Reliable Grounding - Reliable grounding of rackmounted equipment 
should be maintained. Particular attention should be given to supply 
connections other than direct connections to the branch circuit (e.g., use 
of power strips).