Chapter 3
LEDs, DIP Switches, and Connectors
© National Instruments Corporation
3-5
IP RESET Switch
To clear the CVS-1450 device IP settings, move the IP RESET switch to 
the ON position and reset the CVS-1450 device. Use IP RESET to reset 
the TCP/IP settings when moving the system from one subnet to another or 
when the current TCP/IP settings are invalid.
Resetting the CVS-1450 device with the IP RESET switch in the ON 
position resets the IP address to 0.0.0.0. You can then set up a new network 
configuration for the CVS-1450 device from a development machine on the 
same subnet, or you can use an Ethernet crossover cable to connect the 
CVS-1450 device directly to the development computer.
NO APP Switch
To prevent the CVS-1450 device from automatically running VIs at 
startup, move the NO APP switch to the ON position and reset the 
CVS-1450 device. If the CVS-1450 device becomes inaccessible because 
of a startup program, enable the NO APP switch and reset the CVS-1450 
device.
Enable this switch to prevent the CVS-1450 device default startup program 
or Vision Builder AI from running at startup.
USER 1 Switch (LabVIEW Real-Time Module Users)
The USER 1 switch is user-configurable and has no default functionality. 
You can use the RT Read Switch VI to read the USER 1 switch state and 
perform a custom action based on the current switch state position.