4.6.2  Protection on Twisted-Pair Data Ports 
 
RuggedCom does not recommend the use of CAT-5 cabling of any length for critical real-time 
substation automation applications. However, transient suppression circuitry is present on all 
copper ports to protect against damage from electrical transients and to ensure IEC 61850-3 and 
IEEE 1613 Class 1 conformance. This means that during the transient event communications 
errors or interruptions may occur but recovery is automatic. 
 
RuggedCom also does not recommended to use these ports to interface to field devices across 
distances which could produce high levels of ground potential rise, (i.e. greater than 2500V) during 
line to ground fault conditions.