2.4  Dielectric Strength (HIPOT) Testing 
 
For dielectric strength (HIPOT) testing in the field, users must remove the metal 
jumper located on terminal 2, 4, and 6 of the power supply terminal block.  This 
metal jumper connects transient suppression circuitry to chassis ground and 
must be removed in order to avoid damage to transient suppression circuitry 
during HIPOT testing. Figure 21 shows the proper HIPOT test connections and 
should be followed to avoid damage to the device.   
  
 
Figure 21: Dielectric Strength (HIPOT) Testing 