RuggedCom RSG2288 用户手册

下载
页码 43
Installation 
The number of IRIG-B devices that can be connected to the AM or PWM sources 
is dependent on the cabling type and length as well as the input impedances of 
the devices. Figure 31 shows a simplified circuit diagram of the interface between 
an IRIG-B source and connected devices. 
 
Vs
Rs
Rc
R
L
/N
Source
Cabling
Device
 
Figure 31: IRIG-B Simplified Schematic 
 
The maximum number of devices (N) that can be connected to the source is 
determined by checking if the source current (I
S
) required to drive the connected 
devices is less than the maximum drive current the source can provide, and 
verifying that the load voltage (V
L
) the connected devices see is greater than the 
minimum required voltage. Please refer to section 3.6.1 for specifications of the 
IRIG-B output port. 
35 
RuggedCom
® 
RuggedSwitch
® 
RSG2288 Installation Guide rev103