RuggedCom RSG2288 用户手册
Technical Specifications
3.6 PTP Card Specifications
IRIG-B PWM Input
Parameter
Typical Value
Input Voltage
TTL-Compatible
Input Impedance
> 200 kΩ
3.6.1 IRIG-B Outputs
IRIG-B003 PWM Output
Parameter
Typical Value
Output Current (I
S
) 100
mA
Output Voltage (V
S
) 5
V
p-p
Output Impedance (R
S
) 50
Ω
Table 15: IRIG-B PWM Output Specifications
IRIG-B123 AM Output
Parameter
Typical Value
Carrier Frequency
1 kHz
Modulation Depth
3:1 ±10%
Output Current (I
S
) 24
mA
Output Impedance (R
S
) 10
Ω
Output Voltage (V
S
) 6
V
p-p
Table 16: IRIG-B AM Output Specifications
3.7 Operating Environment
Parameter
Range
Comments
Ambient Operating
Temperature
-40 to 85
C
Ambient Temperature as
measured from a 30cm radius
surrounding the center of the
enclosure.
Ambient Relative
Humidity
5% to 95%
Non-condensing
Ambient Storage
Temperature
-40 to 85
C
39
RuggedCom
®
RuggedSwitch
®
RSG2288 Installation Guide rev103