RuggedCom RSG2288 用户手册

下载
页码 43
Type Tests 
4.2  IEEE 1613 Type Tests 
IEEE Test 
IEEE 
1613 
Clause 
Description 
Test Levels 
Enclosure Contact 
+/- 8kV 
C37.90.3 9 
ESD 
Enclosure Air 
+/- 15kV 
C37.90.2 
Radiated RFI 
Enclosure ports 
35 V/m 
Signal ports 
+/- 4kV @ 2.5kHz 
D.C. Power ports 
+/- 4kV 
A.C. Power ports 
+/- 4kV 
C37.90.1 7 Fast 
Transient 
Earth ground ports 
+/- 4kV 
Signal ports 
2.5kV common mode @ 1MHz 
D.C. Power ports 
2.5kV common & differential mode @ 1MHz
C37.90.1 7  Oscillatory 
A.C. Power ports 
2.5kV common & differential mode @ 1MHz
Signal ports 
5 kV (Failsafe Relay) 
D.C. Power ports 
5 kV 
C37.90 6 H.V. 
Impulse 
A.C. Power ports 
5 kV 
Signal ports 
2kVAC 
D.C. Power ports 
1.5kVDC 
C37.90 6 
Dielectric 
Strength 
A.C. Power ports 
2kVAC 
Table 18 - IEEE 1613 Type Tests 
 
Notes: 
  If the unit contains copper ports, the IEEE 1613 conformance is Class 1 (During 
disturbance errors may occur but recovery is automatic).  
  If the unit contains all fiber ports, the IEEE 1613 conformance is Class 2 (During 
disturbance no errors will occur). 
4.3   IEC Environmental Type Tests 
Test 
Description 
Test Levels 
Severity 
Levels 
IEC 60068-2-1 
Cold 
Temperature 
Test Ad 
-40 deg. C, 16 Hours 
N/A 
IEC 60068-2-2 
Dry Heat 
Test Bd 
+85 deg. C, 16 Hours 
N/A 
IEC 60068-2-30 
Humidity (Damp 
Heat, Cyclic) 
Test Db 
95% (non-condensing), 55°C, 6 
cycles 
N/A 
IEC 60255-21-1 
Vibration 
2g @ (10-150) Hz 
Class 2 
IEC 60255-21-2 
Shock 
30g @ 11 ms 
Class 2 
Table 19 - Environmental Type Tests 
 
Note: 
Class 2 refers to “Measuring relays and protection equipment for which a very high 
security margin is required or where the vibration levels are very high, (e.g. shipboard 
application and for severe transportation conditions).”
 
42 
RuggedCom
® 
RuggedSwitch
® 
RSG2288 Installation Guide rev103