9  Electro-Magnetic Compatibility (EMC) 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
113
 
9.1.6 
EMC Compliance Tests 
Table 9-4 
EMC Compliance Table 
Model Remarks 
Environment – General Industrial 
6SE6411-6U***-**A1 
1UA1**-**U** 
Unfiltered units, all voltages and powers. 
Environment – Filtered Industrial (All EU countries for year 2002) 
6SE6411-6B***-**A1 
1UA1**-**B** 
Filtered units all voltages and powers. 
Environment – Filtered for residential, commercial and light industry 
6SE6411-6B***-**A1 
1UA1**-**B** 
Filtered units all voltages and powers. 
* Denotes any value is allowed. 
 
9.1.7 
MICROMASTER 411 – EMC Compliance 
The MICROMASTER 411 inverters will, when correctly installed and put to their 
intended use, satisfy the requirements of the EEC Directive 89/336/EEC 
concerning electromagnetic compatibility. 
If the guidelines on installation to reduce the effects of electromagnetic interference 
are followed, the devices are sutiable for installation in machines. According to the 
machinery directive, these machines must be separately certified. 
Table 9-5 below lists the measured results for emissions of an immunity to 
interference for the MICROMASTER 411 inverters. 
Table 9-5 
MICROMASTER 411 Measured Results 
Test Standard 
Measurement 
Test Value 
Limit Value 
RFI Emisions 
Conducted via Mains Cable 
150 kHz to 30 MHz 
Unfiltered – not tested Class B 
 
Emitted by the inverter 
30 MHz to 1 GHz 
All devices – Class A