10  Engineering Information 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
117
 
 
Figure 10-1  Current Limit Interaction 
 
10.1.1 Current 
Monitoring 
Accuracy 
Table 10-1 shows sample results comparing current measured with a current 
scope, and the current displayed on the inverter, using measurements taken from a 
variety of inverters at various switching frequencies, current loads, frequency 
setpoints and cable lengths. 
Table 10-1 
Measured Current Monitoring Accuracy 
Inverter 
Frame Size B, 400 V  
1,5 kW 
Frame Size C, 400 V 
3,0 kW 
Switching frequency 
4 kHz 
4 kHz 
Load on inverter 
Nominal load 
4 A 
Nominal load 
7,7 A 
Frequency setpoint 
45 Hz 
45 Hz 
Scope current (long cable)* 
4,00 A 
7,70 A 
Drive current 
4,05 A 
7,46 A 
% difference (inverter/scope)* 
1,32 % 
-3,9 %