2  Installation 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
34 
6SE6400-5CA00-0BP0  
2.5.2 
Line and Motor Connections  
 
WARNING 
This equipment must be grounded.
 
♦ 
Isolate the electrical power supply before making or changing connections to 
the unit. 
♦ 
MICROMASTERS must not be connected to a higher voltage supply. 
♦ 
Ensure that the motor is configured for the correct supply voltage 380 V to 
480 V three-phase supply. 
♦ 
When synchronous motors are connected or when coupling several motors in 
parallel, the inverter must be operated with voltage/frequency control 
characteristic (P1300 = 0, 2 or 3). 
 
 
CAUTION 
After connecting the power and motor cables to the proper terminals, make sure 
that the cover has been replaced properly before supplying power to the unit!
 
 
 
NOTICE 
♦ 
Ensure that the appropriate circuit-breakers/fuses with the specified current 
rating are connected between the power supply and inverter (see Section 
7.5). 
♦ 
Use Class 1 75
o
C copper wire only. For tightening torque see Section 7.3. 
♦ 
To tighten up the power terminal screws use either a 4-5 mm flat bladed 
screwdriver or a 2pt Pozidrive Head screwdriver. 
Access to the power and motor terminals 
The procedure for accessing the power and motor terminals on the 
COMBIMASTER 411 & MICROMASTER 411 Inverter is illustrated in Figure 2-10.