页码 164
3  Commissioning 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
46 
6SE6400-5CA00-0BP0  
3.3.1 
Ramp Times Using Jumpers 
Inverter ramp times are set using a series of 5 jumpers (fit jumper to enable 
function). Each jumper must be set as shown in Table 3-1. 
The jumpers overwrite the default settings or the ramp times specified using 
BOP/AOP/IBN software. 
The inverter recognizes when jumper values have been set when power is re-
applied. 
CAUTION 
Jumpers have priority in setting ramp times. When the jumpers are removed the 
ramp times are not changed. It is then possible to change ramp times via the 
parameters (using the BOP). 
Ramp times apply to Ramp Up and Ramp Down. Jumper locations are as shown in 
Figure 3-3.  
 
Figure 3-3 
Ramp Time Jumpers 
Using up to 5 jumpers allows ramp times to be set between 1 - 240 s. Also see 
Table 3-1. 
Table 3-1 
Ramp Time Adjustment Jumpers 
Time [s]  X20  X10  5 s  2 s  1 s 
 
Time [s] X20  X10  5 s  2 s  1 s 
 
 
 
 
×
 
 70 
 
×
 
×
 
×
 
 
 
 
 
×
 
 
 80 
 
×
 
×
 
×
 
×
 
 
 
 
×
 
×
 
 90 
×
 
×
 
 
×
 
×
 
 
 
×
 
 
 
 100 
×
 
 
×
 
 
 
 
 
×
 
 
×
 
 120 
×
 
 
×
 
 
×
 
 
 
×
 
×
 
 
 140 
×
 
 
×
 
×
 
 
 
 
×
 
×
 
×
 
 150 
×
 
×
 
×
 
 
 
10 
 
×
 
 
 
×
 
 160 
×
 
 
×
 
×
 
×
 
20 
 
×
 
 
×
 
 
 180 
×
 
×
 
×
 
 
×
 
30 
 
×
 
 
×
 
×
 
 210 
×
 
×
 
×
 
×
 
 
50 
 
×
 
×
 
 
 
 240 
×
 
×
 
×
 
×
 
×
 
60 
 
×
 
×
 
 
×