5  System Parameters 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
68 
6SE6400-5CA00-0BP0  
5.1 
Introduction to System Parameters 
Parameters can only be changed by using the Basic Operator Panel (BOP), 
the Advanced Operator Panel (AOP) or Serial Interface. 
NOTE 
 
Full details of the COMBIMASTER 411 /MICROMASTER 411 Parameters can 
be found in the separate document “COMBIMASTER 411/MICROMASTER 
411 – Parameter List”. 
 
This document is included in the CD ROM delivered with the product. 
 
Parameters may be changed and set (using the BOP) to adjust the desired 
properties of the inverter, such as ramp times, minimum and maximum frequencies 
etc. The parameter numbers selected and the setting of the parameter values are 
indicated on the optional five-digit LCD display. 
 
rxxxx indicates a display parameter, Pxxxx a setting parameter. 
 
P0010 initiates “Quick Commissioning”. Set P0010 to 1. 
 
The inverter will not run unless P0010 is set to 0 after it has been accessed. 
This function is automatically performed if P3900 > 0. 
 
P0004 acts as a filter, allowing access to parameters according to their 
functionality group. 
 
If an attempt is made to change a parameter that cannot be changed in this 
status, for example, cannot be changed whilst running or can only be changed 
in quick commissioning, then 
 will be displayed. 
 
Busy Message 
In some cases - when changing parameter values - the display on the BOP 
shows  
 for maximum of five seconds. This means the inverter is 
busy with tasks of higher priority. 
 
5.1.1 Access 
Levels 
There are three access levels available to the user; Standard, Extended and 
Expert. The level of access is set by parameter P0003. For most applications, the 
Standard and Extended levels are sufficient. 
The number of parameters that appear within each functional group depends on 
the access level set in parameter P0003. For further details regarding parameters, 
see the Parameter List on the Documentation CD-ROM.