7.2 
Case Size Rating Information 
Table 7-2 
Case Size B 
MICROMASTER 411 / COMBIMASTER 411 
Frame size:  
2 pole 
4 pole 
 
71 
71 
 
71 
80 
 
80 
80 
 
80M 
90S 
 
90S 
90S 
Motor Output Rating 
0.37 kW 
0,5 hp 
0.55 kW 
0,75 hp 
0.75 kW 
1,0 hp 
1,1 kW 
1,5 hp 
1,5 kW 
2,0 hp 
Operating Input Voltage (rms) 
3 AC 380 V – 480 V 
±
 10 %  
Operating Input Frequency 
47 – 63 Hz 
Output Frequency 
2 pole 
4 pole 
 
0 – 650 Hz 
 
Inrush Current 
< 4 A 
Input Current (rms) 
1,6 A  
2,1 A  
2,8 A  
4,2 A  
5,8 A  
Output Current (max) 
1,2 A 
1,6 A 
2,1 A 
3,0 A 
4,0 A 
Power Supply fuse 
10 A 
Power Supply Lead  
cross-section 
4 mm
(max.)
 
 
Table 7-3 
Case Size C 
MICROMASTER 411 / COMBIMASTER 411 
Frame size:  
2- pole 
4- pole 
 
90L 
100L 
 
100L 
100L 
Motor Output Rating 
2,2 kW 
3,0 hp 
3,0 kW 
4,0 hp 
Operating Input Voltage (rms) 
3 AC 380 V – 480 V 
±
 10 %  
Operating Input Frequency 
47 – 63 Hz 
Output Frequency 
2 pole 
4 pole 
0 – 650 Hz 
Inrush Current 
< 7.7 A 
Input Current (rms) 
7,8 A  
10 A  
Output Current (max) 
5,9 A 
7,7 A 
Power Supply fuse 
16 A 
Power Supply Lead  
cross-section 
4 mm
2