FieldServer FS-8700-31 用户手册

下载
页码 26
FS-8700-31 
Siemens 
TIWAY 
           Page 
of 
23 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldserver.com
 
4.4.4. 
Reading TIWAY data map descriptor examples 
4.4.4.1. 
Reading data from contiguous PLC data memory locations 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length, 
C01_RAW16_PLC01, RAW16_Data, 
0, RDBC, 
PLC_01, 
IE_Ladder, 
0, 
10, 
 
Scan_Interval 
0s 
 
The above map descriptor will continuously read 10 data elements starting from address 0 of type “IE_Ladder” from 
PLC_01. The data will be stored in the data array called “RAW16_Data” from an offset of 0. 
 
4.4.4.2. 
Reading data from random PLC data memory locations 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type,  TIWAY_Address_List, Length, 
C02_RAW16_PLC01, RAW16_Data, 
10, 
RDBC,  PLC_01,  Variable, 
9, 
2, 
 
Scan_Interval 
0s 
 
The above map descriptor will continuously read 2 data elements from address 5 and 9 of type “Variable” from 
PLC_01. The data will be stored in the data array called “RAW16_Data” from an offset of 10. The data will be 
stored at offsets 10 and 11. 
 
 
 
 
 
 
4.4.4.3. 
Reading Drum_Count_Preset data from contiguous PLC data memory locations 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length, 
C08_RAW16_PLC01, RAW16_Data, 
70, 
RDBC, PLC_01,  Drum_Count_Preset, 
0, 
5,