Fujitsu C122-E119EN 用户手册

下载
页码 109
Item
Description
Weight [kg (lb)] (*2)
150 (330)
Air conditioning
requirements
Maximum heat output [kJ/h (BTU/h)]
14,400 (13,649)
Exhaust air
flow [m
3
/min
(ft
3
/min)] (*3)
FAN at low speed (Low)
14 (494)
FAN at normal speed (Normal)
21 (742)
FAN at high speed (High)
24 (848)
Temperature
and humidity
requirements
(*4)
Operating
Temperature [°C (°F)]
(*5)
Humidity [%RH]
20 to 80
Maximum wet-bulb
temperature [°C (°F)]
29 (84.2)
Non-operating (*6) Temperature [°C (°F)]
0 to 50 (32 to 122)
Humidity [%RH]
8 to 80
Maximum wet-bulb
temperature [°C (°F)]
29 (84.2)
Noise [dB] (*7) (*8)
61
Acoustic power level [B] (*8)
7.8
Allowable
vibration [m/
s
2
 (gal)]
Operating (including standby state)
4.0 (400) (synthetic seismic
waves)
Non-operating (*9)
10.0 (1000) (synthetic
seismic waves)
Allowable dust concentration [mg/m
3
]
0.15
Power
requirements
Input voltage and number of phases
200 to 240 VAC ±10%
Single phase
Frequency and fluctuation range
50/60 Hz +2/-4%
Maximum
power
consumption/
apparent
power
Operating
Input voltage: 200 V
4.00 kW / 4.21 kVA
Standby
Input voltage: 200 V
95 W / 126 VA
Power factor (*10)
0.95 or more
Rush current [A] (Inrush time) (*11)
20 or less
Leakage current [mA] (*12)
3.5 or less
*1 The dimensions do not include protrusions.
*2 The values are for the device with all options installed.
      However, the values do not include the weight of mounted rack-mount rails (7 kg) and cables.
      You can use the following formula to calculate the weight of the device based on its configuration:
  Equipment weight = 86 + (11 x A) + (8 x B) + (2 x C)
PRIMEQUEST 1000 Series Hardware Installation Manual
CHAPTER 1 Installation Information
8
C122-H004-07EN