FIGURE A.7 Conditions regarding rack posts
 
A: Space for attaching the device front panel: 483 mm (19.0 in.) or more
B: Distance between holes on the left and right device mounting posts (common to the front and rear posts): 465
mm (18.3 in.)
C: Distance between the left and right posts (common to the front and rear posts): 450 mm (17.7 in.) or more
D: EIA standard, universal pitch
E: Length of each side of a square hole: 9 to 9.5 mm (0.354 to 0.374 in.)
 
Other conditions
Besides structural conditions, the following conditions must also be considered.
- Cooling of devices mounted in the rack
Install the rack such that the temperature inside the rack satisfies the temperature conditions in 
.
Especially, cover the front of empty spaces in the rack and take other such necessary measures to prevent
exhaust air from devices from recirculating to the air intake.
- Securing the maintenance work area (service area)
Secure the service area required for the maintenance work performed by a Fujitsu certified service engineer.
used, determine the service areas.
 