Fujitsu C122-H007-01EN 用户手册
![Fujitsu](https://files.manualsbrain.com/attachments/6c4642b33d2edbd09f94719c20a133aa0e862902/common/fit/150/50/80a45702a21fefb1823bce6851e87db450dccf7792cb572ebc8a90330a68/brand_logo.png)
CHAPTER 2 Connected Information
2.3 Power cable connection
2.3 Power cable connection
27
C122-H007-01EN
200 V Dual Power Feed Configuration with Power Distribution Box Connection
It is necessary to arrange six PSUs, six power cables (200 V IEC60320 C20) and four power distribution
boxes (200 V IEC60320 C19×3type) for 200 V dual power feed configuration.
When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution
panel. See “
boxes (200 V IEC60320 C19×3type) for 200 V dual power feed configuration.
When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution
panel. See “
FIGURE 2.20 200 V Dual Power Feed Configuration with Power Distribution Box Connection
Number
Description
(1)
Power distribution box (200V C 19
3 type)
2.3.3 Power Cable Connections (PCI_Box)
This section shows the figure of input power of PCI_Box.
Remarks
While configuring redundant power feed and dual power feed in this device, configure the same power feed
to PCI_Box.
Remarks
While configuring redundant power feed and dual power feed in this device, configure the same power feed
to PCI_Box.
100 V Configuration (single power feed, no redundant power feed)
It is necessary to arrange PSU and power cable (100 V NEMA 5-15P) for 100 V configuration (Single power
feed, no redundant power feed).
feed, no redundant power feed).
FIGURE 2.21 100 V Configuration (Single power feed, no Redundant power feed)
Number
Description
(1)
Customer distribution panel AC 100V AC#0 system