FieldServer FS-X20 用户手册

下载
页码 13
 
 
 
 
 
 
 
 
 
 
 
Start-up guide 
Page 2 
FS-X20 Series FieldServer Start-up Guide (07-2005) 
1.  Pre-Installation Check List 
1.1.  Supplied equipment 
The following components are supplied: 
• 
FS-X20  Series  FieldServer,  loaded  with 
Modbus  RTU  driver,  SMT  Ethernet 
driver and any other drivers ordered.
1
 
• 
FS-X20 Series Start-up Guide (T17005) 
• 
FieldServer 
Configuration 
Manual 
(T17003) 
• 
FieldServer Utilities Manual (T17009) 
• 
Driver  Manual(s)  specific  to  all  Drivers 
ordered with the FieldServer. 
• 
Utility CD – note that the Utilities support 
the following platforms only: 
• 
Windows XP 
• 
Windows 2000 
• 
Windows NT 
• 
Windows 98 
• 
Any  additional  Diskettes  related  to 
special  files  configured  for  a  specific 
FieldServer. 
• 
Additional  components  as  required  -. 
See  Driver  Manual  Supplement  for 
details 
• 
An  accessory  bag  consisting  of  the 
following: : 
• 
DB9F/RJ45  Connection  Adapter. 
(Part Number FS-8917-02) 
• 
7-ft 
Cat5 
cable 
with 
RJ45 
connectors  at  both  ends  (Part 
Number FS-8915-10) 
• 
RS-232  Mini  Tester,  25-pin  (Part 
Number FS-8915-13) 
• 
RS-485  connector  (Part  Number 
FS-SPA59137) 
• 
Set  of  four  different  connectors 
DB9M, DB9F, DB25M, DB25F (Part 
Number FS-8915-11) 
• 
Power Supply  
• 
Connector for power (SPA59136) 
 
 
1.2.  Start-up 
•  Read  this  Start-up  Guide  in  conjunction 
with  the  Configuration  Manual,  the 
                                                 
1
 
Note  that  a  default  configuration  file  has 
already  been  loaded  onto  the  FieldServer.  
Check  the  Driver  Manual  and  the  FieldServer 
Configuration  Manual  for  further  information  on 
this file.
 
Driver  Manual(s)  and  the  Utilities 
manual.   
•   
•  The  power  socket  mates  with  a 
pluggable terminal block, connector, that 
is supplied separately (SPA59136).  The 
terminal  block  is  manufactured  by 
Phoenix  Contact,  model  MSTB,  (PN 
1754465),  No.30-12  AWG,  5-7  in/lbs 
torque. 
•   
•  USE COPPER CONDUCTORS ONLY 
•  Select an external power supply certified 
for  safety,  for  the  correct  destination 
country  and  an  output  rating,  which  is 
considered a NEC Class 2 circuit or is a 
SELV  Limited  power  source  with  the 
following ratings: 
•  9-30  VDC,  1A;      OR  24  VAC,  50/60Hz, 
0.5A 
•   
•  INPUT VOLTAGE SPECIFICATION 
•  24 VAC FLOATING 
•  Using a grounded VAC will cause 
irreparable damage to the product. 
•   
•  The  operating  environment  for  the 
product is 0 to 60°C (32 to 140°F). 
•   
•   
•   
•