GE GFK0579B 用户手册

下载
页码 154
8
Series 90–70 Remote I/O Scanner User’s Manual – July 1992
116
Display and Clear Faults from Logicmaster  90–70   
The content of the PLC and I/O Fault Table displays depends on whether the
programmer is communicating with the PLC or a remote drop.
I/O Fault Table at the PLC
The content of the fault display at the PLC depends on the revision level of the Bus
Controller.   With a Bus Controller that is version 4.0 or later, when a fault occurs on a
remote drop, the I/O Fault Table shows the Drop ID and the rack and slot within the
remote drop where the fault has occurred:
33#0.4
Drop ID
Rack
Slot
Remote Drop Fault
  
Drop ID#, rack, slot
Genius Bus Fault
  
rack, slot, bus, 
  bus address
|PROGRM |TABLES |
STATUS
 |       |       |LIB    |SETUP  |FOLDER |UTILTY |PRINT
1
plcrun
 2
passwd
 3
plcflt
 4
io flt
 5
plcmem
 6
blkmem 
7
refsiz
 8
sweep
  9
clear
 10
zoom
 
>                                                                               
                          I / O   F A U L T   T A B L E
                               
 TOP FAULT DISPLAYED: 0001                    TABLE LAST CLEARED: 09–21 08:00:00
        TOTAL FAULTS: 0007                    ENTRIES OVERFLOWED: 0000          
   FAULT DESCRIPTION: OPEN WIRE                    PLC DATE/TIME: 10–14 10:05:13
 
   FAULT     CIRC  REFERENCE        FAULT            FAULT       DATE    TIME
  LOCATION    NO.    ADDR.        CATEGORY           TYPE         M–D  H: M: S 
 ___________ _____ _________ ___________________ ________________ _____ ________
  
33#0.4      6   %AI0101    CIRCUIT FAULT       ANALOG FAULT     10–12 08:12:20
 0.3.1.5          %Q01009    ADD’N OF DEVICE                      10–12 08:12:22
 MAINPLC     RUN/ENABLE    7MS SCAN  ONLINE  L4 ACC: WRITE CONFIG CONFIG EQUAL
 PLC C: LESSON                  PRG: LESSON  
 REPLACE
I/O Fault Table Display with a Rev. 3 Bus Controller
If the Bus Controller is a rev. 3 version, it cannot transfer to the PLC the detailed fault
information provided by a Remote I/O Scanner. Instead, a rev. 3 Bus Controller reports
any fault from a remote drop as a 
GENA
 
fault.
Fault Clearing
To clear the fault table, press the Clear key.