WR / WC Series Woodburning Fireplace
20014528
Chimney Requirements - Offset Installations
 
0   0   0   0   0  
3"  
11"
  1   0   0   0   0  
8¹⁄₄"  
20"
  0   1   0   0   0   11¹⁄₄"   25¹⁄₄"
  2   0   0   0   0   13¹⁄₂"   29¹⁄₄"
  1   1   0   0   0   16¹⁄₂"   34¹⁄₄"
  0   0   1   0   0   20¹⁄₄"   40³⁄₄"
  2   1   0   0   0   21³⁄₄"   43¹⁄₂"
  0   0   0   1   0   26¹⁄₄"   51¹⁄₄"
  0   1   1   0   0   28¹⁄₂"   55¹⁄₄"
  1   0   0   1   0   31¹⁄₂"   60¹⁄₄”
  0   1   0   1   0   34¹⁄₂"   65¹⁄₂"
  0   0   2   0   0   37¹⁄₂"   70³⁄₄"
  1   1   0   1   1   41¹⁄₂"   77³⁄₄"
  0   0   1   1   1  
45"   83³⁄₄"
  0   1   2   0   1   47¹⁄₄"   87¹⁄₂"
  0   0   0   2   1  
51"  
94"
  0   1   1   1   1   53¹⁄₄"  
98"
  0   0   3   0   1   56¹⁄₄"   103¹⁄₄"
  0   1   0   2   1   59¹⁄₄"   108¹⁄₂"
  0   0   2   1   1   62¹⁄₄"   113¹⁄₂"
  0   1   3   0   1   64¹⁄₂"   117¹⁄₂"
  0   0   1   2   1   68¹⁄₄"  
124"
  0   1   2   1   1   70¹⁄₂"  
128"
  0   0   0   3   1   74¹⁄₄"   134¹⁄₂"
  0   1   1   2   2  
78"   140³⁄₄"
  0   0   3   1   2  
81"  
146"
  0   1   0   3   2  
84"   151¹⁄₄"
  0   0   2   2   2  
87"   156¹⁄₂"
  0   1   3   1   2   89¹⁄₄"   160¹⁄₄"
  0   0   1   3   2  
93"   166³⁄₄"
  0   1   2   2   2   95¹⁄₄"   170³⁄₄"
  0   0   0   4   2   99¹⁄₄"   177³⁄₄"
  0   1   1   3   2   101¹⁄₄"   181³⁄₄"
  0   0   3   2   2   104¹⁄₄"   186¹⁄₄"
  0   1   0   4   2   107¹⁄₄"   191¹⁄₂"
  0   0   2   3   2   110¹⁄₄"   196³⁄₄"
  0   1   3   2   3  
114"   203¹⁄₄"
  0   0   1   4   3   117³⁄₄"   209³⁄₄"
  0   1   2   3   3  
120"   213¹⁄₂"
  0   0   0   5   3   123³⁄₄"  
220"
30˚ elbow Offsets
1' 1¹⁄₂' 3' 4'
Chimney
Support
Offset
Rise
Notes:   G + H cannot exceed 20 feet.
 
Air Space Clearances: SK8 (2-wall) = 1¹⁄₂" and "S" Series (3-wall) = 2"  
Illustration Key
The following safety rules apply to offset 
installations (letters correspond with il-
lustration above): 
A. Height of the chimney is measured 
from the hearth to the chimney exit.
 
   
WR/WC400   WR/WC500
Maximum:  
90'0" 
90'0"
Minimum:
  Without Elbows  12' 6" 
12' 6"
  With 2 Elbows*  14' 6" 
14' 6"
  With 4 Elbows*  21' 0" 
21' 0"
b. Do not use more than 4 elbows per 
chimney.
Attach the straps of the return (top) elbow 
to a structural framing member.
The offset (first) elbow of any pair does 
not have straps.
IWF269
C. The chimney cannot be more than 30˚ 
(45˚ in Canada) from the vertical plane in 
any installation*.
D. The maximum length of the angled run 
of the total chimney system is 20 feet. (G 
plus H cannot exceed 20 feet.)
e. A chimney support (Model SKCS8) 
is required every 6 feet of angled run of 
chimney. Chimney supports are required 
for every 30 feet and 60 feet (SK8 pipe) 
or 20 feet and 40 feet (3-wall pipe) of ver-
tical chimney height above the hearth. 
Determine the offset distance of your 
chimney arrangement from the centerline 
of the fireplace to the centerline of the 
chimney where it is to pass through the 
first ceiling. 
NOTe: This offset distance may not be 
your full offset distance. See Examples 2 
and 3.
FP282
MBUF
5/26/96
OFFSET
RISE
IWF282
  *  In Canada, two (2) SK845 are allowed.
Fig. 6  Chimney system requirements.
D
RISE
B
G
H
B
OFFSET
C
E
6 FT.
G
H
A
HEARTH
FLOOR
CHIMNEY
SECTION
CHIMNEY FLUE EXIT
ELBOW
FP269
MBUF
5/16/96
rev. 5/25
30° 
OFFSET
ELBOW
30° 
OFFSET
ELBOW
30° 
RETURN
ELBOW
30°  
RETURN
ELBOW
SKCS8 
SUPPORT
Example 1
Example 2
Example 3