Chapter 2
Function Reference — AO_Change_Parameter
NI-DAQ FRM for PC Compatibles
2-32
©
 National Instruments Corporation
Output Enable
On some of the devices, you can disable the output even when the waveform generation is in 
progress. You can use this feature to bring the output to a known level at any time.
On DAQArb 5411 devices, there is a relay just in front of the I/O connector. By disabling the 
output, this relay switches so that the I/O connector output shorts to ground. The waveform 
generation can still continue, but no signal appears at the I/O connector output. You can 
enable or disable the output at any time.
To change the output enable setting, set paramID to 
ND_OUTPUT_ENABLE
.
Output Impedance
On some of the devices, you can select the output impedance to match the impedance of 
the load.
Output impedance of 50 
Ω
 is good for testing most of the devices. You can use output 
impedance of 75 
Ω
 for video testing. If you select an output impedance of 0 
Ω
, you should be 
driving an unterminated load (that is, a load with a very high input impedance).
To change the output impedance setting, set paramID to 
ND_IMPEDANCE
.
Note
The values are set up in milliOhms (m
Ω
).
Table 2-9.  Parameter Setting Information for Output Enable
Device Type
Per Channel 
Selection Possible
Legal Range 
for paramValue
Default Setting 
for paramValue
DAQArb AT-5411 
DAQArb PCI-5411
4451 devices
4551 devices
Yes
ND_YES
 and 
ND_NO
ND_NO
Table 2-10.  Parameter Setting Information for Output Impedance
Device Type
Per Channel 
Selection Possible
Legal Range 
for paramValue
Default Setting 
for paramValue
DAQArb AT-5411 
DAQArb PCI-5411
Yes
0, 50,000, and 
75,000
50,000