MODELS SIG
80
 / SIG
80
M / SIG
110
 / SIG
110
D / SIG
110
H
 
Motion Model: SIG80M 
Factory setting: low speed airflow 40CFM, time delay 15 minutes.
 
Humidity Model: SIG110H 
DIMENSION
 
 
5-2. Motion control mode: Turn the POWER switch on to operate at 
motion control mode. When motion is detected, the fan will run at 
full speed  and the LED indicator will be amber. When motion is 
not detected, the fan will continue to run at the full speed until 
the user -adjustable time delay has elapsed, and then will 
automatically change to the user-adjustable low speed airflow. 
The LED indicator will be green.
5-3. Humidity control mode: Turn the POWER switch on to operate 
at humidity control mode - the LED indicator will be blue. When 
the ambient humidity is higher than the user -adjustable set-point, 
the fan will run at full speed. When the ambient humidity is lower 
than the set-point, the fan will continue to run at the full speed 
until a 10-minute time delay has elapsed, and then will auto 
matically change to the user-adjustable low speed airflow.
 
5-4. Full speed mode: Turn the MODE switch on to operate at full 
speed mode - the LED indicator will be amber. 
 
5-5. Humidity tolerance is about ±10%. Long -time operation will 
influence the detecting precision as dust accumulates. The 
humidity switch may need to be adjusted. 
 
Factory setting: low speed airflow 60CFM, humidity 60%RH
 
MAINTENANCE WARNING:
Disconnect the power source before working on the unit. Routine 
maintenance must be done every year. 
CAUTION: 
1. Never use gasoline, benzene, thinner or any other such chemi-
cals to clean the ventilating fan. 
2. Do not allow water to enter the mot or
3. Do not soak resin parts in water over 60°C (140°F)
CLEANING 
1. Pull down the springs to remove the grille. 
2. Wash and clean the grille. (Use non -abrasive kitchen detergent 
and wipe dry with a new cloth.) 
3. Remove dust and dirt from the ventilating fan
4. Using a cloth dampened with non -abrasive kitchen detergent, 
remove any dirt from ventilating fan. Wipe dry with a new cloth
5. Replace the grille
WARRANTY 
 
DELTA ELECTRONICS THREE YEAR LIMITED WARRANTY
    Delta Electronics Inc. (“Delta Electronics”) warrants to the 
original consumer purchaser in the USA that the Breez 
ventilation fan products will be free from defects in material or 
workmanship. This warranty is limited to three (3) years from 
the original date of purchase.
Limitations and Exclusions 
1. During the warranty period, a replacement for any defective 
product will be supplied free of charge for installation by the 
consumer. The warranty provided herein does not cover 
charges for labor or other costs incurred in the troubleshooting, 
repair, removal, and installation service.
2. All returns of defective parts or products must include the 
product model number, and must be made through an 
authorized Delta Electronics distributor. Authorized returns 
must be shipped prepaid. Repaired or replacement products 
will be shipped by Delta Electronics 
F.O.B. shipping point.
3. Delta Electronics shall not be liable for any indirect, inciden-
tal, consequential, punitive, or special damages arising out of or 
in connection with products use or performance, regardless of 
the form of action whether in contract, tort (including 
negligence), strict product liability or otherwise. 
4. This warranty does not extend to uorescent lamp starters 
and tubes.
5. The warranty does not cover if user does not comply with 
manufacturer’s installation manual.
6. To qualify for warranty service, you must notify Delta 
Electronics at the address or telephone number below.
7. Delta Electronics shall have no liability to the original 
owner-user with respect to any defect caused by abuse, misuse, 
neglect, improper transportation or storage, improper testing, 
improper installation, improper operation, improper use, 
improper maintenance, improper repair, improper alteration, 
improper modifcation, tampering or accident of products or 
parts thereof, or unusual deterioration or degradation of 
products or parts thereof due to a physical environment 
beyond the requirements of products’ specifcations.
Address: 4405 Cushing Parkway, Fremont, CA 94538
US Toll Free Number: 1-888-979-9889
SPECIFICATIONS 
Model No.  
Voltage  
(V) 
Frequency  
(Hz) 
Power 
@ 0.1”SP 
(W) 
Air Flow 
@ 0.1”SP 
(CFM) 
Weight 
(lb.) 
Power   
(W) 
Note 
SIG80 
120 
60 
8.2 
80 
10 
18.0 
Single Speed  
SIG80M 
120 
60 
8.2 
80 
10 
18.0 
Motion Sensor  
SIG110 
120 
60 
12.7 
110 
10 
23.0 
Single Speed  
SIG110H  
120 
60 
12.7 
110 
10 
23.0 
Humidity 
Sensor  
SIG110D  
120 
60 
12.7 
110 
10
23.0 
Dual Speed  
Note: Design and specifications subject to change without notice.