Protect PV.500_MH Operating Instructions 
 
80000043212 BAL 
45 of 68 
LED signals: 
Green/red flashes:
 
Configuration can be selected via the ter-
minal  
(up to 30 seconds after restarting) 
Green on: 
Operating status; no external communica-
tion via X2 and X5 
Green flashes: 
Data transmission on the serial interfaces 
(X2 or X5)  
Red on: 
Fault 
Description of serial interfaces
Port 1: Serial interface X2 
The potential-free RS232 serial interface at connector X2 supports 
the AEG-specific CBSER protocol for parameter setting and moni-
toring purposes. Special service tools can be used to monitor and 
manage the equipment locally and (with the aid of the COM serv-
er) remotely via a network. This is also the port used for configur-
ing the assembly's interfaces. 
1
5
6
9
 
Figure 14 
Serial D-sub connector X2 
Port 1 (X2): RS232 pin assignment 
Pin number  Signal Description 
RxD  PC receiving data from the MCC 
TxD  PC sending data to the MCC 
GND  Interface reference potential 
Housing 
 
INV housing potential 
 
Please use a 1:1 data cable for configuration purposes. 
Port 2: Serial interface X5 (internally wired to X91) 
The potential-free RS485 interface at connector X5 supports the 
Modbus protocol for integration into higher-level monitoring sys-
tems. 
1
5
6
9