CAPACITY CONTROLS
Dual Fan Motors—The dual fan motor package is available as 
a proven energy saving capacity control option. It consists of 
furnishing a high efficiency motor, a 1200 RPM, low speed motor, 
two sets of drives and belts, extended fan shaft and motor bases 
on opposite sides of the blower. A UL control-starter panel is 
available as a completely wired package for one point connection.
Variable Speed Drive—A Variable Speed Drive automatically 
minimize the tower’s noise level during periods of reduced load 
and/or reduced ambient temperature without sacrificing the 
system’s ability to maintain a constant cold water temperature. This 
is a relatively inexpensive solution, and can pay for itself quickly in 
reduced energy costs.
Electric Damper Controls—An electric damper control package 
is available as an accessory for modulating the internal damper 
system. A proportional solid state actuator is factory mounted 
below the fan scroll and attached to the damper shaft by 
connecting linkage. A sensing bulb connected to the actuator by 
a capillary tube is normally mounted in the unit pan water basin 
for monitoring the system. However, when specified, a pressure 
control may be supplied for field mounting to allow direct head 
pressure control. An end switch located inside the motor actuator 
may be adjusted to cycle the fan motor on for pressure rise and off 
when dampers close.
COIL CASING INSULATION
In order to further reduce the heat loss from the unit coil, insulation 
factory installed on exterior coil panels is available. A protective 
coat of paint is applied to the insulation for protection from the 
weather elements.
POSITIVE CLOSURE DAMPERS
Many times during unit shutdown with fan and pump off, it is 
desirable to conserve the amount of heat loss from the process 
fluid. For those applications, closure dampers are available for this 
installation at the air discharge of the fluid cooler. The damper 
package is designed to prevent convective air flow through the 
idle unit thus minimizing the heat loss. Installation of the closure 
dampers requires all wiring to be completed in the field. An electric 
actuator is factory mounted, however controls are to be supplied by 
others. The damper actuator should be wired into the field control 
system to allow the dampers to fully open when the fan cycles on 
and close when the fan cycles off. The actuator requires a 115V 
power supply
ELECTRONIC WATER LEVEL CONTROL
The electronic water level control package provides a constant 
and accurate means of monitoring water level in the unit. For this 
reason, it is often recommended for those installations which 
require year round operation in low ambient conditions.
The complete package includes an electric float switch with stilling 
chamber which is factory installed in the pan section of the unit. 
An electric solenoid valve for water make-up is shipped loose for 
remote installation. All wiring must be provided in the field by 
others.
PUMP STRAINER
Pump intake extension and a cleanable non-ferrous pump strainer in 
an easy access location is available.
MODIFICATIONS TO WATER DISTRIBUTION SYSTEM
Various package are available to provide manual or automatic 
change-over as a backup system in the event of a spray pump 
failure
PAN HEATER
The use of a remote sump tank located indoors is a common form 
of pan water freeze protection for evaporative cooling equipment. 
However, for those installations which will not allow this type of 
system, freeze protection may be provided by electric immersion 
heaters or steam or hot water coils installed in the pan.
The electric heater package consists of immersion heaters installed 
in the pan to provide efficient even heat distribution. Standard 
heaters are selected to provide approximately 40°F pan water at 
-10°F ambient temperature. A low water cutout switch is supplied 
to prevent heater operation when the elements are not completely 
submerged. The heaters are monitored by a sump thermostat 
with remote sensing bulb located in the pan water. All heaters and 
controls are factory installed for field wiring by others.
NOTE: Pan heater packages are designed to prevent pan water 
freezing during unit shutdown with fans and pump idle.
CAPACITY BOOSTER COIL
A finned coil mounted on top of the eliminator section is available 
primarily for applications with high entering fluid temperatures 
or for applications where dry operation under low entering air 
temperatures is anticipated. Copper tube with aluminum or copper 
fin coils are available.
VIBRATION ISOLATORS
Spring type vibration isolator rails may be supplied for field 
installation, most units will require an intermediate rigid steel 
framework between the isolators and the base of the unit to 
provide adequate structural support for the unit. Consult Recold 
sales representative for recommendations on any vibration isolation 
application.
STAINLESS STEEL CONSTRUCTION
300 stainless steel construction is offered as an option for sump 
pan and upper casing panels.