Carrier 17/19EX 用户手册

下载
页码 437
prevent possible piping stress and damage during the transfer of refrigerant from vessel to 
vessel during the leak test process, or any time refrigerant is transferred. Adjust the springs 
when the refrigerant is in operating condition, and when the water circuits are full.
Refrigerant Tracer 
Carrier recommends the use of an environmentally acceptable refrigerant tracer for leak 
testing with an electronic detector or halide torch. 
Ultrasonic leak detectors also can be used if the machine is under pressure.
Leak Test Machine
Due to regulations regarding refrigerant emissions and the difficulties associated with 
separating contaminants from refrigerant, Carrier recommends the following leak test 
procedures. See 
 for an outline of the leak test procedures. Refer to 
 and 
 for refrigerant pressure/temperature values and to 
 section.
Do not use air or oxygen as a means of pressurizing the machine. Some mixtures 
of HFC-134a and air can undergo combustion.
WARNING
!
WARNING