Adding Refrigerant
Follow the procedures described in 
 section.
Removing Refrigerant
When the optional pumpout system is used, the 17/19EX refrigerant charge may be 
transferred to a storage vessel, or within the utility vessel. Follow procedures in th
 section when removing refrigerant.
Adjusting the Refrigerant Charge
If the addition or removal of refrigerant is required for improved machine performance, follow 
the procedures given under the 
 section.
Always use the compressor pumpdown function in the Control Test mode to turn 
on the evaporator pump and lock out the compressor when transferring refriger-
ant. Liquid refrigerant may flash into a gas and cause possible freeze-up when the 
machine pressure is below 30 psig (207 kPa) for HFC-134a.
WARNING
!
WARNING