The chiller also maintains a start-to-start timer and a stop-to-start timer. These timers limit 
how soon the machine can be started. See the 
 section 
for operational information. 
Occupancy Schedule 
This schedule determines when the chiller is either occupied or unoccupied. 
Each schedule consists of from one to 8 occupied/unoccupied time periods, set by the 
operator. These time periods can be enabled to be in effect, or not in effect, on each day of the 
week and for holidays. The day begins with 0000 hours and ends with 2400 hours. The machine 
is in OCCUPIED mode unless an unoccupied time period is in effect. 
The machine will shut down when the schedule goes to UNOCCUPIED. These schedules 
can be set up to follow the building schedule or to be 100% OCCUPIED if the operator wishes. 
The schedules also can be bypassed by forcing the Start/Stop command on the PIC Status 
screen to start. The schedules also can be overridden to keep the unit in an OCCUPIED mode 
for up to 4 hours, on a one-time basis. 
 shows a schedule for a typical office building time schedule, with a 3-hour, off-peak 
cool down period from midnight to 3 a.m., following a weekend shutdown. Example: Holiday 
periods are unoccupied 24 hours per day. The building operates Monday through Friday, 7:00 
a.m. to 6:00 p.m., with a Saturday schedule of 6:00 a.m. to 1:00 p.m., and includes the Monday 
midnight to 3:00 a.m. weekend cool-down schedule.