Whenever the motor current demand limit set point is reached, it activates a capacity 
override, again with a 2-step process. Exceeding 110% of the rated load amps for more than 30 
seconds will initiate a safety shutdown. 
The compressor high lift (surge prevention) set point will cause a capacity override as well. 
When the surge prevention set point is reached, the controller normally will only hold the guide 
vanes from opening. If so equipped, the hot gas bypass valve will open instead of holding the 
vanes.
High Discharge Temperature Control 
If the discharge temperature increases above 200 F (93 C), the guide vanes are 
proportionally opened to increase gas flow through the compressor. If the leaving chilled water 
temperature drops 5° F (2.8° C) below the control point temperature, machine will enter the 
recycle mode.