6. Configuration
6. 1. Communication parameters
Configure the following parameters in the 
[1.9 - COMMUNICATION]
 
(
COM-)
 menu, 
[Uni-Telway/Modbus]
 
(
UtL-)
 submenu: 
[Protocol]
 
(
PrO)
[Bit rate]
 
(
bdr)
 and 
[Format]
 
(
FOr)
.
These parameters can only be modified when the motor is stopped. Modifications can only be taken into account by the drive following a
power break.
Parameter
Possible values
Terminal display
Default value
[Protocol]
 
(
PrO)
Uni-Telway
Modbus/RTU
Modbus/ASCII
[Unitelway]
 
(
UtE)
[Modbus RTU]
 
(
rtU)
[Modbus ASCII]
 
(
ASC)
[Unitelway]
 
(
UtE)
[Address]
 
(
AdrC)
0 to 247
[0]
 
(
0)
 to 
[247]
 
(
247)
Value taken from the address switches
[Bit rate]
 
(
Bdr)
4800 bps
9600 bps
19,200 bps
[4800 Bd]
 
(
 
4 8)
[9600 Bd]
 
(
 
9 6)
[19200 Bd]
 
(
 
19 2)
[19.2 Kbps]
 
(
 
19 2)
[Format]
 
(
FOr)
In RTU mode only:
8 data bits, odd parity, 1 stop bit
8 data bits, even parity, 1 stop bit
8 data bits, no parity, 1 stop bit
8 data bits, no parity, 2 stop bits
[8-O-1]
 
(
8o1)
[8-E-1]
 
(
8E1)
[8-N-1]
 
(
8n1)
[8-N-2]
 
(
8n2)
[8-O-1]
 
(
8o1)
In RTU and ASCII modes:
7 data bits, odd parity, 1 stop bit
7 data bits, even parity, 1 stop bit
7 data bits, odd parity, 2 stop bits
7 data bits, even parity, 2 stop bits
[7-O-1]
 
(
7o1)
[7-E-1]
 
(
7E1)
[7-O-2]
 
(
7o2)
[7-E-2]
 
(
7E2)