8. 2. Modes
RTU mode
The Modbus RTU frame contains no message header byte, nor end of message bytes. 
It is defined as follows:
The data is transmitted in binary code.
CRC16: Cyclic redundancy check parameter.
The end of the frame is detected on a silence greater than or equal to 3.5 characters.
The format used for the frames in the rest of this document is RTU mode.
ASCII mode
The structure of the Modbus ASCII frame is as follows:
Header: By default, ":" = 16#3A. Two other characters are possible: "CR" = 16#0D and "LF" = 16#0A.
LRC: The 2's-complement of the modulo 256 sum (in hexadecimal format) of the frame (excluding the header and end characters) before
ASCII coding.
Example: Write a value of 10 to logic address word 9001 (16#2329) on slave 2
Identical request and response:
In hexadecimal format
In ASCII format